Temporary fluid transfer and cooling systems. Modern liquid cooling and thermoregulation systems for industrial processes that ensure the highest efficiency and safety of work in all conditions.
A wide range of device parameters – from 6kW to 2000kW. Comprehensive services. Rental of equipment and installations. Professional expertise.

| Reference | GFT10 MTA | GFT20 MTA | GFT50 MTA | GFT80 MTA |
|
|---|---|---|---|---|---|
| Compressors | 1 śruba | 1 śruba | 1 śruba | 2 śruby | |
| Design output | KW kcal/h | 6.6 5675 | 15 12900 | 41 35000 | 70 60200 |
| Chilled water outlet temp | °C | +7/+12 °C | +7/+12 °C | +7/+12 °C | +7/+12 °C |
| Design Flow with a dT of 5°c | m3/h | 2,5 m3/h / 30 mCE | 2, m3/h / 30 mCE | 8 m3/h / 35 mCE | 13 m3/h / 28 mCE |
| Brine system | ℃ | -10°/-5°C | -10°/-5°C | -10°/-5°C | -10°/-5°C |
| Max. outlet water temperature | ℃ | +15 °C | +15 °C | +15 °C | +15 °C |
| Design ambiant temperature | ℃ | +35 °C | +35 °C | +35 °C | +35 °C |
| Refrigerant | R410A | R410A | R407C | R410A | |
| Ampere rating | A | 7A | 25 A | 35 A | 63 A |
| Power usage | kW | 3,8 | 12,9 | 18 | 36 |
| Electric Supply | V | 400V | 400V | 400V | 400V |
| Type of power cable | mm² | 5 x 6² | 5 x 6² | 4 x 6² | 4 x 16² |
| kVA genset | 10 | 20 | 60 | 100 | |
| Camlock fluid connection | Ø | DN25 | DN25 | DN50 | DN50 |
| Pump | Integrated | Integrated | Integrated | Integrated | |
| Length | m | 1,250 | 2,5 | 2,00 | 2,50 |
| Width | m | 560 | 1,05 | 1,00 | 1,05 |
| Height | m | 810 | 2,3 | 1,65 | 2,3 |
| Sound pressure @10 meters | dB (A) | 52 | 53 | 55 | 58 |
| Weight (empty) | kg | 450 | 800 | 1000 | 1300 |

| Reference | GFT130 MTA | GFT180 MTA | GFT210 MTA | GFT270 CIAT |
|
|---|---|---|---|---|---|
| Compressors | 4 scroll | 4 scroll | 4 scroll | 4 scroll | |
| Design output | KW kcal/h | 123 105000 | 178 153080 | 208 178000 | 263 226180 |
| Chilled water outlet temp | °C | +7/+12 °C | +7/+12 °C | +7/+12 °C | +7/+12 °C |
| Design Flow with a dT of 5°c | m3/h | 23 m3/h / 31 mCE | 30 m3/h / 31 mCE | 39 m3/h / 26 mCE | 45 m3/h / 31.2 mCE |
| Brine system | ℃ | -10°/-5°C | -10°/-5°C | -10°/-5°C | -10°/-5°C |
| Max. outlet water temperature | ℃ | +15 °C | +15 °C | +15 °C | +15 °C |
| Design ambiant temperature | ℃ | +35 °C | +35 °C | +35 °C | +35 °C |
| Refrigerant | R410A | R410A | R410A | R410A | |
| Ampere rating | A | 104 A | 142 A | 177 A | 214 A |
| Power usage | kW | 44.8 | 79 | 90 | 102 |
| Electric Supply | V | 400V | 400V | 400V | 400V |
| Type of power cable | mm² | 4 X 35 ² | 4 X 95 ² | 4 X 95 ² | 4 x 95² |
| kVA genset | 125 | 175 | 175 | 200 | |
| Camlock fluid connection | Ø | DN50 | DN50 | DN100 | DN100 |
| Pump | Integrated | Integrated | Integrated | Integrated | |
| Length | m | 3,05 | 3,62 | 3,62 | 4,72 |
| Width | m | 2,45 | 2,45 | 2,40 | 2,39 |
| Height | m | 2,60 | 2,15 | 2,35 | 2,35 |
| Sound pressure @10 meters | dB (A) | 61 | 62 | 58 | 64 |
| Weight (empty) | kg | 2100 | 2287 | 3700 | 4400 |

| Reference | GFT340 MTA | GFT450 MTA | GFT430 MTA | GFT520 CIAT |
|
|---|---|---|---|---|---|
| Compressors | 4 scroll | 6 scroll | 2 scroll | 2 scroll | |
| Design output | KW kcal/h | 332 285000 | 444 381000 | 429 368000 | 510 438000 |
| Chilled water outlet temp | °C | +7/+12 °C | +7/+12 °C | +7/+12 °C | +7/+12 °C |
| Design Flow with a dT of 5°c | m3/h | 62 m3/h / 33 mCE | 77 m3/h / 35 mCE | 85 m3/h / mCE | 96 m3/h / 30 mCE |
| Brine system | ℃ | -10°/-5°C | -10°/-5°C | -10°/-5°C | -8°/-4°C |
| Max. outlet water temperature | ℃ | +15 °C | +15 °C | +15 °C | +15 °C |
| Design ambiant temperature | ℃ | +35 °C | +35 °C | +35 °C | +35 °C |
| Refrigerant | R410A | R410A | R410A | R410A | |
| Ampere rating | A | 263 A | 329 A | 378 A | 413 A |
| Power usage | kW | 128 | 175 | 196 | 196 |
| Electric Supply | V | 400V | 400V | 400V | 400V |
| Type of power cable | mm² | 4 x 95² | 4 x 240 ² | 4 X 240 ² | 7 X 240 ² |
| kVA genset | 175 | 175 | 196 | 196 | |
| Camlock fluid connection | Ø | DN100 | DN100 | DN100 PN | DN100 PN |
| Pump | integrated | Mpt450 | Mpt520 | Mpt520 | |
| Length | m | 4,72 | 4,77 | 6,65 | 4,77 |
| Width | m | 2,39 | 2,42 | 2,20 | 2,42 |
| Height | m | 2,35 | 2,8 | 2,45 | 2,88 |
| Sound pressure @10 meters | dB (A) | 64 | 60 | 55 | 68 |
| Weight (empty) | kg | 4400 | 4930 | 5400 | 5350 |

| Reference | GFT520 CIAT | GFT600 TRANE | GFT620 MTA |
|
|---|---|---|---|---|
| Compressors | 6 scroll | 2 scroll | 9 scroll | |
| Design output | KW kcal/h | 520 447000 | 606 521000 | 618 531000 |
| Chilled water outlet temp | °C | +7/+12 °C | +7/+12 °C | +7/+12 °C |
| Design Flow with a dT of 5°c | m3/h | 89 m3/h / 30 mCE | 100 m3/h / 30 mCE | 105 m3/h / 30 mCE |
| Brine system | ℃ | -8°/-4°C | 0°/+5°C | -10°/-5°C |
| Max. outlet water temperature | ℃ | +15 °C | +15 °C | +15 °C |
| Design ambiant temperatur | ℃ | +35 °C | +35 °C | +35 °C |
| Refrigerant | R134A | R134A | R410A | |
| Ampere rating | A | 358 A | 421 A | 427 A |
| Power usage | kW | 196 | 232 | 243 |
| Electric Supply | V | 400V | 400V | 400V |
| Type of power cable | mm² | 4 X 240 ² | 7 x 240² | 7 x 240 ² |
| kVA genset | 320 | 500 | 500 | |
| Camlock fluid connection | Ø | DN100 | DN100 | DN100 |
| Pump | Mpt520 | Mtp600 | Mtp600 | |
| Length | m | 6,91 | 6,22 | 6,75 |
| Width | m | 2,20 | 2,44 | 2,42 |
| Height | m | 2,26 | 2,66 | 2,8 |
| Sound pressure @10 meters | dB (A) | 64 | 60 | 62 |
| Weight (empty) | kg | 6550 | 6750 | 6850 |

| Reference | GFT750 MTA | GFT750 CIAT | GFT920 CIAT |
|
|---|---|---|---|---|
| Compressors | 3 śrubowa | 2 śrubowa | 2 śrubowa | |
| Design output | KW kcal/h | 743 639000 | 728 626000 | 920 791000 |
| Chilled water outlet temp | °C | +7/+12 °C | +7/+12 °C | +7/+12 °C |
| Design Flow with a dT of 5°c | m3/h | 140 m3/h / 30 mCE | 125 m3/h / 10 mCE | 160 m3/h / 30 mCE |
| Brine system | ℃ | -10°/-5°C | -10°/-5°C | 0°/+5°C |
| Max. outlet water temperature | ℃ | +15 °C | +15 °C | +15 °C |
| Design ambiant temperature | ℃ | +35 °C | +35 °C | +35 °C |
| Refrigerant | R134A | R134A | R134A | |
| Ampere rating | A | 600 A | 568 A | 637 A |
| Power usage | kW | 362 | 244 | 284 |
| Electric Supply | V | 400V | 400V | 400V |
| Type of power cable | mm² | 7 X 240 ² | 7 X 240 ² | 7 X 240 ² |
| kVA genset | 500 | 500 | 800 | |
| Camlock fluid connection | Ø | DN100 PN | DN100 PN | DN100 PN |
| Pump | Mtp750 | Mtp750 | Mtp920 | |
| Length | m | 6,75 | 6,50 | 9,86 |
| Width | m | 2,42 | 2,25 | 2,45 |
| Height | m | 2,88 | 2,43 | 2,80 |
| Sound pressure @10 meters | dB (A) | 69 | 67 | 59 |
| Weight (empty) | kg | 7688 | 6850 | 9500 |

| Reference | PFT50 MTA | PFT60 MTA | PFT70 MTA | PFT150 MTA | PFT300 MTA |
|
|---|---|---|---|---|---|---|
| Compressors | 1 Scroll | 2 Scroll | 2 Scroll | 3 Scroll | 3 Scroll | |
| Design cooling ouput | KW | 4 | 53.6 | 68.8 | 68.8 | |
| Chilled water outlet temperature | °C | +7/+12 °C | +7/+12 °C | +7/+12 °C | +7/+12 °C | +7/+12 °C |
| Design heating output | °C | 48,6 | 63,4 | 84,1 | 170 | 320 |
| Max. hot water outlet T° | m3/h | +40/+45 °C | +40/+45 °C | +40/+45 °C | +40/+45 °C | +40/+45 °C |
| Design flow with a dT of 5°c | m3/h | 7 m3/h / 26 mCE | 10 m3/h / 26 mCE | 13 m3/h / 26 mCE | 28,5 m3/h / 35mCE | 54 m3/h / 39 mCE |
| Cool brine system | ℃ | -8/-4 °C | -8/-4 °C | -8/-4 °C | -8/-4 °C | -8/-4 °C |
| Max. hot water outlet T° | ℃ | +40/+45 °C | +40/+45 °C | +40/+45 °C | +40/+45 °C | +40/+45 °C |
| Design Ambient T° - Cooling | ℃ | -5 / + 46 °C | -5 / + 46 °C | -5 / + 46 °C | -5 / + 46 °C | -5 / + 46 °C |
| Design Ambient T° - Heating | ℃ | -10 / + 20 °C | -10 / + 20 °C | -10 / + 20 °C | -10 / + 20 °C | -10 / + 20 °C |
| Refrigerant | R 410 A | R 410 A | R 410 A | R 410 A | R 410 A | |
| Ampere rating | A | 144 A/ 21kW | 181 A/ 27kW | 207A/ 36kW | 213A/ 36kW | 386A/ 147kW |
| Electric supply | V | 400V | 400V | 400V | 400V | 400V |
| Type of power cable | mm² | 5g16 ² | 4 x 16 ² | 4 x 16 ² | 4 x 16 ² | 4 x 16 ² |
| Camlock fluid connection | Ø | DN50 | DN50 | DN50 | DN50 | DN50 |
| Pump | integrated | integrated | integrated | integrated | integrated | |
| Length | m | 2,00 | 2,400 | 2,400 | 3,600 | 4,600 |
| Width | m | 0,900 | 1,000 | 1,000 | 2,200 | 2,200 |
| Height | m | 1,850 | 2,450 | 2,450 | 2,450 | 2,450 |
| Sound pressure @10 meters | dB (A) | 54 | 55 | 57 | 64 | 64 |
| Weight (empty) | kg | 1000 | 1300 | 1400 | 2700 | 4200 |


| Model HEATCRAFT | DRYTB | DRYTB | |
|---|---|---|---|
| Summer dissipated power | KW | 700 | 837 |
| Inlet / outlet air temperature | °C | +30/+47 | +30/+47 |
| Inlet / outlet water temperature | °C | +60/+50 | +60/+50 |
| Design air flow | m3/h | 145 000 m3/h | 150 333 m3/h |
| Winter dissipated power | KW | 1167 | 1395 |
| Inlet / outlet air temperature | ℃ | +30/+47 | +30/+47 |
| Inlet / outlet water temperature | ℃ | +60/+50 | +60/+50 |
| Design water flow | m3/h | 71,78 m3/h | 71,78 m3/h |
| Fluid | Water | Water | |
| Rating | A | 32 | 32 |
| Electric supply | V | 400 V | 400 V |
| Type of cable | mm² | 5 x 6 ² | 5 x 6 ² |
| Camlock fluid connection | Ø | DN100 | DN100 |
| Pump | EXTERNAL | EXTERNAL | |
| Length | m | 6,35 | 6,35 |
| Width | m | 2,31 | 2,4 |
| Height | m | 960 | 1,5 |
| Sound pressure @10 meters | dB (A) | 59 | 59 |
| Weight (empty) | kg | 1250 | 1600 |

| Model NEMESIS | CTAT130 | CTAT250 | CTAT350 | CTAT350 | |
|---|---|---|---|---|---|
| Design output | KW | 130 | 264 | 264 | 500 |
| In / out water temperature | °C | +6/+47 | +6/+47 | +6/+47 | +6/+47 |
| In / out air temperature | °C | +60/+50 | +60/+50 | +60/+50 | +60/+50 |
| Design air flow | m3/h | 10 000 | 20 000 | 20 000 | 40 000 |
| Design water flow | m3/h | 22 | 45 | 45 | 45 |
| Speed variator | yes | yes | yes | yes | |
| Pressure | pa | 850 | 850 | 850 | 850 |
| Ducting diameter | 2 | 2 x 500 | 3 x 500 | 1 x 800 | 4 x 500 |
| Return air ducting | 2 | 2 x 500 | 1 x 500 | 1 x 500 | |
| Power | kW | 7,5 | 11 | 11 | 16 |
| Rating | A | P17 32A | P17 32A | P17 32A | P63 63A |
| Electric supply | V | 400 V | 400 V | 400 V | 400 V |
| Type of cable | mm² | 4 x 6 ² | |||
| Camlock fluid connection | Ø | DN50 | DN50 | DN50 | DN100 |
| Temperature regulator | 3-way valve | 3-way valve | 3-way valve | 3-way valve | |
| Length | m | 2,6 | 2,7 | 2,7 | 4 |
| Width | m | 1,2 | 1,2 | 1,2 | 1,2 |
| Height | m | 1,58 | 2,25 | 2,25 | 2,25 |
| Sound pressure @10 meters | dB (A) | 61 | 62 | 63 | 63 |
| Weight (empty) | kg | 760 | 1050 | 1050 | 2800 |

| Model LENNOX / CIAT | CRT50 | CRT100 | CRT175 | |
|---|---|---|---|---|
| Design cooling output | KW | 48 | 96 | 173 |
| Design heating output | KW | 38 | 82 | 126 |
| Max. air flow | m3/h | 10 000 | 20 000 | 30 000 |
| Max. outside temperature | °C | 35 | 35 | 35 |
| Air inlet temperature | °C / %HR | +25/50 | +25/90 | +27/40 |
| Air outlet temperature | °C / %HR | +11/90 | +11/90 | +14/91 |
| Pressure | pa | 600 | 600 | 850 |
| Ducting diameter | mm | 1 x 500 | 2 x 500 | 2 x 800 |
| Return air ducting | mm | 1 x 500 | 2 x 500 | 2 x 800 |
| Power | kW | 55 | 83 | 160 |
| Rating /at start | A | 86/171 | 125/313 | 156/286 |
| Electric supply | V | 400 V | 400 V | 400 V |
| Type of cable | mm² | 4 x 35 ² or P17 125 | 4 x 50² or P17 125 | 4 x 95² |
| Power battery capacity | KW | 27 (+12/25°C) | 38 (+12/25°C) | 54 (+12/25°C) |
| Length | m | 2,6 | 2,7 | 4,81 |
| Width | m | 1,2 | 1,2 | 2,20 |
| Height | m | 1,58 | 2,25 | 2,10 |
| Sound pressure @10 meters | dB (A) | 61 | 63 | 75 |
| Weight (empty) | kg | 760 | 2100 | 2895 |

| Reference | HEATCRAFT | EVAB50 |
|---|---|---|
| Design output | KW | 54 |
| Fans air flow | m3/h | 32 000m3/h |
| Inlet / outlet temperature | °C | -8° / -4°C |
| Ambient T° | °C | 2 |
| Design water flow | m3/h | 71,78 m3/h |
| Design brine flow | -10°/-5°C | |
| Fluid | monopropylene | WATER |
| Rating (defrost) | A | 52 |
| Electrical supply | V | 400 V TRI +T |
| Type of cable | mm² | 2 x 5 G6 ² |
| Fans electric connection | P17 32 A | |
| Defrost electric connection | P 17 63 A | |
| Camlock fluid connection | Ø | DN50 |
| Length | m | 4,3 |
| Width | m | 1,05 |
| Height | m | 1,50 |
| Sound pressure @10 meters | dB (A) | 56 |
| Weight (empty) | kg | 650 |

| REFERENCE | AEROT5 | |
|---|---|---|
| Design heating output | KW | 47 |
| Air flow | m3/h | 6450 |
| Operating mode @15° outside T° | T° | 80/60 |
| Rating | A | 2,85 |
| Design cooling output | KW | 11 |
| Aif flow | m3/h | 6450 |
| Operating mode @25° outside T° | T° | 7/12 |
| Electric connection | V | 230 V 50 Hz |
| Length | m | 0,742 |
| Depth | m | 0,606 |
| Height | m | 0.513 |
| Weight | kg | 46 |
| Length, framed | m | 0,800 |
| Depth, framed | m | 0,800 |
| Height, framed | m | 1,200 |
| Weight | kg | 64 |

| Reference | TIB65 | TIB1500 | TIB73 | |
|---|---|---|---|---|
| Design output | KW | 6.5 | 15 | 7.3 |
| Operating temperature | °C | +8/+35 | +8/+35 | +8/+35 |
| Blowing | plenum | plenum | 3 x 125 | |
| Air flow | m3/h | 1500 | 3500 | 960 |
| Treated surface | m3 | 156 | 360 | 145 |
| Evacuation | Outdoor 30 ml maxi | Outdoor 30 ml maxi | Gaine 300 |
|
| Control panel | 1 | Manual | Manual | Manual |
| Electric cables | included | included | included | |
| Required power | KW | 2.5 | 5.5 | 11 |
| Rating | A | 12 A | P17 32A | P17 32A |
| Supply | 230 V | 400 V | 230 V | |
| Type of cable | mm | mono | 5g4² | 5g6² |
| Refrigerant | R 407 C | R410A | R 407 C | |
| Length + outdoor unit | m | 1,240/0,520 | 1,074/0,930 | 0,490 |
| Width + outdoor unit | m | 0,850/0,560 | 1,512/0,895 | 0,600 |
| Height + outdoor unit | m | 0,380/0,280 | 0,414/0,641 | 1,303 |
| Sound pressure @10 meters* | dB (A) | 49 | 52 | 59 |
| Weight, empty + outdoor unit | kg | 86/16 | 140/35 | 90 |
Wyrażam zgodę na przechowywanie na urządzeniu z którego korzystam tzw. Plików cookies i wykorzystywanie ich do celów marketingowych, w tym na cele analityczne i profilowania przez TECH-POMP SERWIS SP. Z O.O.
Administrator danych osobowych
TECH-POMP SERWIS SP. Z O.O., ul. Kazimierza Szpotańskiego 10, 04-760 Warszawa
TECH-POMP SERWIS SP. Z O.O. jest wpisana do rejestru przedsiębiorców, prowadzonego przez Sąd Rejonowy Dla M.st.Warszawy w Warszawie, XIII Wydział Gospodarczy Krajowego Rejestru Sądowego pod numerem 0000490913, NIP:952-212-76 03, REGON: 147014784.
Cele przetwarzania danych
1. Świadczenie usług drogą elektroniczną
2. marketing, w tym profilowanie i cele analityczne
3. dopasowanie treści stron internetowych do preferencji i zainteresowań
4. pomiary statystyczne i udoskonalenie usług
Podstawy prawne przetwarzania danych
1. Świadoma zgoda użytkownika – marketing, w tym profilowanie oraz cele analityczne
2. Uzasadniony interes administratora danych – pozostałe cele
Odbiorcy danych
Dane przechowywane są w usługach Google AdWords, Google Analytics i Facebook Ads
Prawa osoby, której dane dotyczą
Prawo żądania sprostowania, usunięcia lub ograniczenia przetwarzania danych; prawo wycofania zgody na przetwarzanie danych osobowych. Inne prawa osoby, której dane dotyczą – ZOBACZ
Informacje dodatkowe
Więcej o zasadach przetwarzania danych w „Polityce prywatności” – ZOBACZ